(4) Attach the Power connector (Plug) to
the GP.
2. Power Supply Cautions
Input and Output signal lines must be
separated from the power control
cables for operational circuits.
To improve noise resistance, be sure
to twist the ends of the power cord
wires before connecting them to the
Power connector (Plug).
The GP unit’s power supply cord should
not be bundled with or kept close to main
circuit lines (high voltage, high current),
or input/output signal lines.
To reduce noise, make the power cord
as short as possible.
If the supplied voltage exceeds the GP
unit’s range, connect a voltage trans-
former.
Be sure to use a low noise power sup-
ply between the line and the ground. If
there is an excess amount of noise,
connect a noise reducing transformer.
The temperature rating of field installed
conductors: 75
o
C only.
Use voltage and noise reducing trans-
formers with capacities exceeding
Power Consumption value.
Must be used with a Class 2 Power
Supply. (24 VDC)
Connect a surge absorber to handle
power surges.
Be sure to ground the surge absorber
(E1) separately from the GP unit (E2).
Select a surge absorber that has a maxi-
mum circuit voltage greater then that of
the peak voltage of the power supply.
3. Grounding Cautions
Be sure to create an exclusive ground
for the Power Cord’s FG terminal. Use
a grounding resistance of 100 , a
wire of 2 mm
2
or thicker, or your coun-
try’s applicable standard.
The SG (signal ground) and FG (frame
ground) terminals are connected inter-
nally in the GP unit.
When connecting the SG line to
another device, be sure that the design
of the system/connection does not pro-
duce a shorting loop.
The grounding wire should have a
cross sectional area greater then
2 mm
2
. Create the connection point as
close to the GP unit as possible, and
make the wire as short, as possible.
When using a long grounding wire,
replace the thin wire with a thicker
wire, and place it in a duct.
Power Connector (Socket)
Power connector (Plug)
FG
+
-
AGP-3300T
Lightening Surge Absorber
E1 E2
FG
GP
GP unit
Other
Equipment
Exclusive Grounding
(BEST)