(4) Attach the Power connector (Plug) to
the GP.
2. Power Supply Cautions
• Input and Output signal lines must be
separated from the power control
cables for operational circuits.
• To improve noise resistance, be sure
to twist the ends of the power cord
wires before connecting them to the
Power connector (Plug).
• The GP unit’s power supply cord should
not be bundled with or kept close to main
circuit lines (high voltage, high current),
or input/output signal lines.
• To reduce noise, make the power cord
as short as possible.
• If the supplied voltage exceeds the GP
unit’s range, connect a voltage trans-
former.
• Be sure to use a low noise power sup-
ply between the line and the ground. If
there is an excess amount of noise,
connect a noise reducing transformer.
• The temperature rating of field installed
conductors: 75
o
C only.
• Use voltage and noise reducing trans-
formers with capacities exceeding
Power Consumption value.
• Must be used with a Class 2 Power
Supply. (24 VDC)
• Connect a surge absorber to handle
power surges.
• Be sure to ground the surge absorber
(E1) separately from the GP unit (E2).
Select a surge absorber that has a maxi-
mum circuit voltage greater then that of
the peak voltage of the power supply.
3. Grounding Cautions
• Be sure to create an exclusive ground
for the Power Cord’s FG terminal. Use
a grounding resistance of 100 Ω , a
wire of 2 mm
2
or thicker, or your coun-
try’s applicable standard.
• The SG (signal ground) and FG (frame
ground) terminals are connected inter-
nally in the GP unit.
When connecting the SG line to
another device, be sure that the design
of the system/connection does not pro-
duce a shorting loop.
• The grounding wire should have a
cross sectional area greater then
2 mm
2
. Create the connection point as
close to the GP unit as possible, and
make the wire as short, as possible.
When using a long grounding wire,
replace the thin wire with a thicker
wire, and place it in a duct.
Power Connector (Socket)
Power connector (Plug)
FG
+
-
AGP-3300T
Lightening Surge Absorber
E1 E2
FG
GP
GP unit
Other
Equipment
Exclusive Grounding
(BEST)